Thursday, July 30, 2015

We love lift stations!

 
Crucial Steps for Maintaining your lift Station:
  1. Wet wells should be pumped out and cleaned at least twice a year, or more often if necessary, to prevent solids and grease build-up. Build-up of solids can create gases that can damage the pump, or sink and get caught in the impeller.
  2. Inspection of submersible pumps should be performed quarterly. Inspection of the impeller should be performed quarterly or when motor hours are not within specifications. The inspections would assure that the impeller is free of debris or any other clogging material.
  3. Inspection and greasing of the check valves should be performed at least twice a year to insure proper working order and to prevent back-flow from the force main to the wet well.
  4. Cleaning and inspections of floats four times a year assure proper performance. The buildup of grease prevents floats from working properly.
  5. Inspection of the light and alarm systems should be performed weekly. An alarm system in working order can alert you to problems immediately.

Call us at 305.620.7005 for a monthly maintenance agreement!